Dry Fire Hydrant Design #52 - Whiteford, Maryland
Email Print RSS Facebook Twitter RSS

By President Mark Davis
October 13, 2022

Last week we finished up our 24th bridge-mount dry fire hydrant installation in Harford County, Maryland....this time back to the Whiteford area. The installation was completed on a State of Maryland bridge over Broad Creek on Graceton Road. Our angle-mount design was used as were suction head and suction strainer products from ETT. Today, we flow tested the device and achieved a flow of 1306 gpm using Engine 611, a 1750 gpm pumper from the Whiteford VFC. Elevation at the site was 390 feet and the lift today just over 13-feet. The project was funded in part with State grant funding.

 
Website Designed and Hosted By: Content Proudly Maintained By: Contact Info:
Firehouse Solutions
www.FirehouseSolutions.com
GBW Associates, LLC
3178 Cardinal Drive
Westminster, MD 21157

Emergency Dial 911
Phone: 443-398-6619