Got Big Water

YouTube
YouTube Channel

Facebook
Facebook Page

Twitter
Twitter Page

Rural Water Supply Operations Seminar
Rural Water Supply Operations Seminar

Water Supply Officer Seminar
Water Supply Officer Seminar

Relay Pumping With Large Diameter Hose
Relay Pumping With Large Diameter Hose

Dry Fire Hydrants Seminar
FD Interface with Fire Protection Systems

Dry Fire Hydrants Seminar
Dry Fire Hydrants Seminar

Dry Fire Hydrant Designs and Installations
Dry Fire Hydrant Designs and Installations

Suction Strainer Flow Test Project:Test Results

Web Counters
Website Visitors
Since
June 22, 2009
3,139,432
Visitors Today
Nov 18, 2024
170



Official PayPal Seal
Dry Fire Hydrant Design #52 - Whiteford, Maryland
Email Print RSS Facebook Twitter RSS

By President Mark Davis
October 13, 2022

Last week we finished up our 24th bridge-mount dry fire hydrant installation in Harford County, Maryland....this time back to the Whiteford area. The installation was completed on a State of Maryland bridge over Broad Creek on Graceton Road. Our angle-mount design was used as were suction head and suction strainer products from ETT. Today, we flow tested the device and achieved a flow of 1306 gpm using Engine 611, a 1750 gpm pumper from the Whiteford VFC. Elevation at the site was 390 feet and the lift today just over 13-feet. The project was funded in part with State grant funding.

 
Website Designed and Hosted By: Content Proudly Maintained By: Contact Info:
Firehouse Solutions
www.FirehouseSolutions.com
GBW Associates, LLC
3178 Cardinal Drive
Westminster, MD 21157

Emergency Dial 911
Phone: 443-398-6619
E-mail: thebigcamel@gotbigwater.com
Copyright © 2024 Firehouse Solutions (A Service of Technology Reflections, Inc.)