Bridge-Mounted Dry Hydrant Installation Flowtest - Gamber, MD
Email Print RSS Facebook Twitter RSS

By President Mark Davis
December 10, 2015

We grabbed a couple of photos from today's flowtest of the new, bridge-mounted dry fire hydrant that we installed in Carroll County, Maryland. Gamber and Community VFC's Engine 134 was used to complete the certification flowtest. The 1,500 gpm pumper took draft using a single length of lightweight, 6-inch suction hose and flowed 1,012 gpm from the high-flow discharge. With a lift of 12-feet, the 1,000 gpm flow was the targe